Vacuum Feed Chlorinators

In these devices, the vacuum created by a flowing water stream through an ejector motivates the chlorine flow from the pressure cylinder. The chlorine regulator and chlorine flowmeter are between the ejector and the chlorine cylinder (see Figure 7.30.10). The partial vacuum developed by the ejector pulls the chlorine gas through the flowmeter. The regulator prevents the flowmeter inlet pressure from reaching atmospheric, eliminating the hazard of chlorine leakage. The rotameter and the rate setting valve are nor-

DIAPHRAGM PUMP WELL PUMP

USUALLY ; OCCASIONALLY (CAN BE OTHER WATER SOURCE)

DIAPHRAGM PUMP WELL PUMP

USUALLY ; OCCASIONALLY (CAN BE OTHER WATER SOURCE)