Reducing Reagent Dead Times

Most of the problem is caused by the extremely small reagent flow rates compared to the size of the reagent pipe and dip tube. The time required to fill up a reagent delivery pipeline or flush out a backfilled dip tube on start-up is the total volume divided by the reagent flow rate. Thus, a few gallons of volume and a one gallon per hour reagent flow can result in a several hours delay before reagent is injected into the process. In gravity flow of reagent, a similar delay occurs whenever the reagent valve changes its opening. Such systems are also subject to control valve capacity variations caused by head changes that may aggravate the rangeability problems. Here are some possible methods to reduce the reagent dead time:

1. Locate throttle valve at injection point.

2. Mount on-off valve (preferably ram type) at injection point.

3. Reduce diameter and length of injector or dip tube.

4. Add a reliable check valve to injector or dip-tube tip.

5. Dilute the reagent upstream.

6. Inject the reagent into vessel side just past baffles.

7. Inject reagent into recirculation line at vessel entry point.

8. Inject reagent into influent line at vessel entry point.

Reagents such as ammonium hydroxide, calcium hydroxide, and magnesium hydroxide are weak bases and have pKa values close enough to many control bands to provide some flattening of the titration curve and some increased controllability from the standpoint of reduced sensitivity to disturbances. However, ammonium hydroxide can flash and create gas bubbles that escape from vessels or choke in-line systems or travel downstream undissolved. Calcium hydroxide (lime) and magnesium hydroxide in solid form may take 15 to 30 minutes to dissolve and in slurry form 5 to 10 minutes to dissolve. This slowness of reagent response adds tremendous dead time to the system. Also, the residence time must be 20 times greater than the dissolution time to insure that less than 1% remains undissolved in the effluent. Consequently, large volumes must be used for pH control, which further increase the loop dead time.

units, or approximately 12.3 pH using the interpolation chart on Figure 7.40.1.

The same procedure is used to illustrate the sensitivity of the process to hysteresis. Increasing the error to 1.5% for a setpoint of 12 gives a low pH of 3.13 and a high pH of 12.39 (10,000 - 14,850 = 4850 on the acid side and 10,000 + 14,850 on the caustic side).

Methods of reducing valve hysteresis, such as pulse interval control and the uses of digital valves, have been proposed. Although these techniques add cost and complexity to the control system, they should be investigated as alternatives to the installation of stirred tanks.

If hysteresis cannot be eliminated, it can profoundly influence pH loop performance unless some other element can be introduced to smooth out this incremental response or, in effect, to reduce the gain of the control loop.