FIG. 7.40.27 Feedback-feedforward control system which keeps the small reagent valve near 50% open.

the addition of upstream reagent. For example, if a downstream volume has either a high or increasing rate of base addition, the existence of an intervening volume of low or decreasing pH would result in shutting off the upstream reagent flow.

The automated start-up and shutdown of pH loops is feasible if redundant sensors configured into voting or median selector systems protect against measurement failure. These operations can be smooth and reliable enough to eliminate the need for operator attention. Most pH loops are too sensitive and nonlinear for manual manipulation, and the elimination of operator actions in most cases greatly improves the performance of the system.