Applications

Most applications involve either titration of the sample or prior treatment in the plant since a single reading on untreated material provides little information. SCD readings are almost independent of the concentration of SS. Titrations can be made with as little sample as will submerge the active part of the instrument.

To estimate the unit treatment demand of a liquid, the environmental engineer must first titrate a volumetric sample with the contemplated treating chemical at a known concentration until he obtains a zero signal. To compare alternative treating chemicals, the environmental engineer titrates identical samples of material with various chemicals. When the effect of a change in pH on treating requirements is studied, the environmental engineer titrates identical samples at various pH levels. This effect can be significant, with chemicals differing considerably in their tolerance of low or high pH.

In the usual treatment plant, the SCD can continuously control the feed of cationic chemicals. The need for changing the rate of adding these chemicals arises from variations in the stream flow rate, changes in the SS loading, the unit demand of the solids, or any combination of these factors. The main advantage of SCD control is its early response to changes. Charge neutralization occurs almost as soon as the treating chemical is dispersed in the stream; therefore, samples can be taken 1 or 2 min after addition of the chemical.

Batch samples taken to the SCD should be adequate to permit rinsing the apparatus several times. Skimming or decanting removes sand, larger solid particles, or oil globules. Since charge is a surface phenomenon and the fines have most of the surface, removing larger particles has little effect. For a continuous sample, a self-cleaning bypass filter should be used (Figures 7.8.2 and 7.8.3). Periodic backflushing or cleaning can also be required.

For continuous control, the SCD measurement signal is fed to a two-mode controller that modulates the chemical feed pump or control valve (see Figure 7.9.11). The maximum and minimum valve opening is limited as a defense against sample loss, which can cause an open loop. Pressure regulators serve as adjustable settings to limit the controller output to a range between the minimum and maximum expected demand.

The SCD controller set point is based on the downstream turbidity measurement. If an existing flow proportioning controller throttles the chemical feed, the SCD controller can influence its ratio set point in a cascade arrangement. Often, more than one chemical is involved, and the environmental engineer must consider a sequence of additions and attendant interactions.

FIG. 7.9.11 Chemical addition control using a streaming current detector.