Change indoor cooling temperature set points from 74 cooling/72 heating to 76 cooling and 70 heating.

Similar effect as night setback, except use 2% per degree setback for continuous operation instead of 1 % for setback.

If local adjustment is available to the tenants, some adjacent areas may have sufficiently different local set points to cause simultaneous heating and cooling, reducing measure savings.

Limiting the local user adjustment to +/- 2 degrees F from nominal set point will help ensure these savings are achieved.