643 Considerations in Steam Trap Sizing

As mentioned earlier in this section, good energy conservation practice demands the efficient removal of condensate from process equipment. It is thus necessary to assure that traps are properly sized for the given condensate load. Grossly oversized traps waste steam by excessive surface heat loss and internal venting, while

Fig. 6.14 Drain orifice.

undersized traps permit accumulation of condensate with resultant loss in equipment heat-transfer effectiveness.

Steam traps are sized based in two specifications, the condensate load (e.g., in lbs/hr or gal/min) and the pressure differential across the trap (in psig). Section 6.3 discussed various methods for estimating condensate loads expected under normal operating conditions.

It is good practice to size the capacity of the trap based on this expected load times a factor of safety to account for peaks at startup and fluctuations in normal operating conditions. It is not unusual for startup condensate loads to be three to four times higher than steady operational loads, and in some applications they may range up to 10 times the steady-state load.

Table 6.10 presents typical factors of safety for condensate capacity recommended by steam trap manufacturers. This indicates typical ranges of factor of safety to consider in various applications. Although there is considerable variation in the recommended values, in both energy and economic terms the cost of oversizing is ordinarily not prohibitive, and conservative safety factors are usually used. The exception to this rule of thumb is in the sizing of disk-type traps, which may not function properly if loaded considerably below design. Drain orifices also must be sized close to normal operating loads. Again, the advice of the manufacturer should be solicited for the specific application in mind.

The other important design specification is the pressure differential over which the trap will operate. Since pressure is the driving force that moves condensate through the trap and on to the receiver, trap capacity will increase, for a given trap size, as the pressure increases. The trap operating-pressure differential is not simply the boiler pressure. On the upstream side of the trap, steam pressure may drop through valves and fittings and through heat-transfer passages in the process equipment. Thus the appropriate upstream pressure is the pressure at the trap inlet, which to a reasonable approximation, can usually be considered to be the process steam pressure at the equipment. Back pressure on the outlet side of the trap must also be considered. This includes the receiver pressure (if the condensate