Removal of Iron and Copper Bearing Deposits

A citric acid-based cleaning method is used to derust the steel shells of heat exchangers containing a high ratio of copper to iron, such as is found in marine air conditioning units. When the fluorocarbon refrigerant becomes contaminated with small amounts of water, corrosive hydrochloric and hydrofluoric acids are formed, causing significant corrosion of the steel shells. These corrosion products must be removed to restore the unit to its proper functioning.

Standard organic acid cleaning techniques are inadequate in this application due to the large amounts of copper oxides present, which are more easily dissolved than the iron oxide and tend to consume the organic acid before the iron oxides can be removed. To overcome this problem, a citrate-based cleaning formulation is modified to contain a reducing agent, which reduces the dissolved copper oxides to precipitated copper metal, which is filtered from the solution. This precipitated copper removal restores the citric acid content of the solution, making it available to dissolve the iron oxides. Any copper metal residue remaining in the system from the first solution is removed in a second step, which is also a citric acid-based solution. The second step also passivates the steel surfaces. The specific formulas for step one and step two are:

• Step 1: Iron and copper oxide removal 3% citric acid, 3% erythorbic acid, pH adjusted to 3.5 with triethanolamine (replaces ammonia, which is corrosive to copper).

• Step 2: Copper metal removal and passivation A second solution is prepared as follows: 3% trisodium citrate, 1.2% triethanolamine, 1% sodium nitrite (Ref 5). It is important that the order of additions be followed precisely to avoid toxic nitrogen oxide gas generation.

Another new application is the use of an EDTA-based solution to dissolve iron- and copper-bearing deposits from pressurized water reactor nuclear power plants. In pressurized water reactor nuclear power plant steam generators, the accumulation of secondary side corrosion deposits and impurities forms sludges that are composed primarily of metal oxides and metallic copper deposits. To remove these deposits, the following solution has been found effective:

Iron solvent

• Ammonium hydroxide to pH 7

• 0.5% inhibitor CCI-80/1 applied at 90 to 120 °C (195 to 250 °F) Copper solvent

• Ammonium hydroxide to pH 7

• 2 to 3% hydrogen peroxide applied at 32 to 43 °C (90 to 110 °F) (Ref 6)